Technolec

PT-508 SERIES

IEC 61850-3 managed DIN-Rail Ethernet switch, with 6 10/100BaseT(X) ports, and 2 100BaseFX multi-mode ports with LC connectors, 1 isolated power supply (24 VDC), -40 to 85°C operating temperature
pt-508-series
IEC 61850-3 and IEEE 1613 compliant
Turbo Ring and Turbo Chain (recovery time
Easy network management by web browser, CLI, Telnet/serial console, Windows utility, and ABC-01
Isolated universal 24 VDC or 48 VDC redundant power inputs
Wide 110/220 VDC/VAC power supply range
Modbus TCP, LLDP, SNMP Inform, QoS, IGMP snooping, VLAN, IEEE 802.1X, HTTPS, SNMPv3, and SSH supported
-40 to 85°C operating temperature range

Ethernet Interface

  • 10/100BaseT(X) Ports (RJ45 connector): 6
  • 100BaseFX Ports (multi-mode LC connector): 2
  • Optical Fiber: Note: When connecting a single-mode fiber transceiver, we recommend using an attenuator to prevent damage caused by excessive optical power.Note: Compute the “typical distance” of a specific fiber transceiver as follows: Link budget (dB) > dispersion penalty (dB) + total link loss (dB).
  • Optical Fiber: 100BaseFX
  • Optical Fiber: Multi-Mode
  • Optical Fiber: Single-Mode
  • Optical Fiber: Fiber Cable Type
  • Optical Fiber: OM1
  • Optical Fiber: 50/125 µm
  • Optical Fiber: G.652
  • Optical Fiber: 800 MHz x km
  • Optical Fiber: Typical Distance
  • Optical Fiber: 4 km
  • Optical Fiber: 5 km
  • Optical Fiber: 40 km
  • Optical Fiber: Wavelength
  • Optical Fiber: Typical (nm)
  • Optical Fiber: 1300
  • Optical Fiber: 1310
  • Optical Fiber: TX Range (nm)
  • Optical Fiber: 1260 to 1360
  • Optical Fiber: 1280 to 1340
  • Optical Fiber: RX Range (nm)
  • Optical Fiber: 1100 to 1600
  • Optical Fiber: 1100 to 1600
  • Optical Fiber: Optical Power
  • Optical Fiber: TX Range (dBm)
  • Optical Fiber: -10 to -20
  • Optical Fiber: 0 to -5
  • Optical Fiber: RX Range (dBm)
  • Optical Fiber: -3 to -32
  • Optical Fiber: -3 to -34
  • Optical Fiber: Link Budget (dB)
  • Optical Fiber: 12
  • Optical Fiber: 29
  • Optical Fiber: Dispersion Penalty (dB)
  • Optical Fiber: 3
  • Optical Fiber: 1
  • Optical Fiber: Note: When connecting a single-mode fiber transceiver, we recommend using an attenuator to prevent damage caused by excessive optical power.Note: Compute the “typical distance” of a specific fiber transceiver as follows: Link budget (dB) > dispersion penalty (dB) + total link loss (dB).
  • Standards: IEEE 802.1D-2004 for Spanning Tree Protocol IEEE 802.1p for Class of Service IEEE 802.1Q for VLAN Tagging IEEE 802.1s for Multiple Spanning Tree Protocol IEEE 802.1w for Rapid Spanning Tree Protocol IEEE 802.1X for authentication IEEE 802.3 for 10BaseT IEEE 802.3ab for 1000BaseT(X) IEEE 802.3ad for Port Trunk with LACP IEEE 802.3u for 100BaseT(X) and 100BaseFX IEEE 802.3x for flow control

Ethernet Software Features

  • Filter: 802.1Q, GMRP, GVRP, IGMP v1/v2c, Port-based VLAN, VLAN unaware
  • Industrial Protocols: EtherNet/IP, Modbus TCP
  • Management: Back Pressure Flow Control, BOOTP, DHCP Option 66/67/82, DHCP Server/Client, Flow control, HTTP, IPv4/IPv6, LLDP, Port Mirror, RARP, RMON, SMTP, SNMP Inform, SNMPv1/v2c/v3, Syslog, Telnet, TFTP
  • MIB: Bridge MIB, Ethernet-like MIB, MIB-II, P-BRIDGE MIB, Q-BRIDGE MIB, RMON MIB Groups 1, 2, 3, 9, RSTP MIB
  • Redundancy Protocols: Link Aggregation, MSTP, RSTP, STP, Turbo Chain, Turbo Ring v1/v2
  • Security: HTTPS/SSL, TACACS+, Port Lock, RADIUS, Rate Limit, SSH
  • Time Management: NTP Server/Client, SNTP, 100BaseFX Single-Mode

Switch Properties

  • IGMP Groups: 256
  • MAC Table Size: 8 K
  • Max. No. of VLANs: 64
  • Packet Buffer Size: 1 Mbits
  • VLAN ID Range: VID 1 to 4094
  • Priority Queues: 4

Serial Interface

  • Console Port: RS-232 (RJ45)

Input/Output Interface

  • Alarm Contact Channels: Resistive load: 1 A @ 24 VDC

Power Parameters

  • Connection: 1 removable 5-contact terminal block(s)
  • Input Voltage: Redundant power inputs, 24 VDC (18 to 36 VDC)
  • Overload Current Protection: Supported
  • Reverse Polarity Protection: Supported
  • Input Current: 0.27 A @ 24 VDC

Physical Characteristics

  • Housing: Aluminum
  • IP Rating: IP40
  • Dimensions (without ears): 60 x 160 x 110 mm (2.36 x 6.30 x 4.33 in)
  • Weight: 995 g (2.21 lb)
  • Installation: DIN-rail mounting, DIN-rail mounting (with optional kit)

Environmental Limits

  • Operating Temperature: -40 to 85°C (-40 to 185°F) Note: Cold start requires minimum of 100 VAC @ -40°C
  • Storage Temperature (package included): -40 to 85°C (-40 to 185°F)
  • Ambient Relative Humidity: 5 to 95% (non-condensing)

Standards and Certifications

  • EMI: EN 55032 Class A, CISPR 32, FCC Part 15B Class A
  • EMS: IEC 61000-4-2 ESD: Contact: 8 kV; Air: 15 kV IEC 61000-4-3 RS: 80 MHz to 1 GHz: 20 V/m IEC 61000-4-4 EFT: Power: 4 kV; Signal: 4 kV IEC 61000-4-5 Surge: Power: 4 kV; Signal: 4 kV IEC 61000-4-6 CS: 10 V IEC 61000-4-8 PFMF IEC 61000-4-11
  • Power Substation: IEC 61850-3, IEEE 1613
  • Safety: UL 508

MTBF

  • Time: 394,238 hrs
  • Standards: Telcordia SR332

Warranty

  • Warranty Period: 5 years
  • Details: See www.moxa.com/warranty

Available Models

Model No. Description Quantity
PT-508-MM-LC-24 IEC 61850-3 managed DIN-Rail Ethernet switch, with 6 10/100BaseT(X) ports, and 2 100BaseFX multi-mode ports with LC connectors, 1 isolated power supply (24 VDC), -40 to 85°C operating temperature
PT-508-MM-SC-48 IEC 61850-3 managed DIN-Rail Ethernet switch, with 6 10/100BaseT(X) ports, and 2 100BaseFX multi-mode ports with SC connectors, 1 isolated power supply (48 VDC), -40 to 85°C operating temperature
PT-508-MM-ST-HV IEC 61850-3 managed DIN-rail Ethernet switch, with 6 10/100BaseT(X) ports and 2 100BaseFX multi-mode ports with ST connectors, 1 isolated power supply (88 to 300 VDC or 85 to 264 VAC), -40 to 85°C operating temperature
PT-508-MM-SC-24 IEC 61850-3 managed DIN-Rail Ethernet switch, with 6 10/100BaseT(X) ports, and 2 100BaseFX multi-mode ports with SC connectors, 1 isolated power supply (24 VDC), -40 to 85°C operating temperature
PT-508-SS-LC-24 IEC 61850-3 managed DIN-rail Ethernet switch, with 6 10/100BaseT(X) ports and 2 100BaseFX single-mode ports with LC connectors, 1 isolated power supply (24 VDC), -40 to 85°C operating temperature
PT-508-MM-ST-48 IEC 61850-3 managed DIN-rail Ethernet switch, with 6 10/100BaseT(X) ports and 2 100BaseFX multi-mode ports with ST connectors, 1 isolated power supply (48 VDC), -40 to 85°C operating temperature
PT-508-MM-LC-HV IEC 61850-3 managed DIN-Rail Ethernet switch, with 6 10/100BaseT(X) ports, and 2 100BaseFX multi-mode ports with LC connectors, 1 isolated power supply (88 to 300 VDC or 85 to 264 VAC), -40 to 85°C operating temperature
PT-508-MM-LC-48 IEC 61850-3 managed DIN-Rail Ethernet switch, with 6 10/100BaseT(X) ports, and 2 100BaseFX multi-mode ports with LC connectors, 1 isolated power supply (48 VDC), -40 to 85°C operating temperature
PT-508-SS-SC-HV IEC 61850-3 managed DIN-rail Ethernet switch, with 6 10/100BaseT(X) ports and 2 100BaseFX single-mode ports with SC connectors, 1 isolated power supply (88 to 300 VDC or 85 to 264 VAC), -40 to 85°C operating temperature
PT-508-MM-ST-24 IEC 61850-3 managed DIN-Rail Ethernet switch, with 6 10/100BaseT(X) ports, and 2 100BaseFX multi-mode ports with ST connectors, 1 isolated power supply (24 VDC), -40 to 85°C operating temperature
PT-508-MM-SC-HV IEC 61850-3 managed DIN-Rail Ethernet switch, with 6 10/100BaseT(X) ports, and 2 100BaseFX multi-mode ports with SC connectors, 1 isolated power supply (88 to 300 VDC or 85 to 264 VAC), -40 to 85°C operating temperature
PT-508-SS-SC-48 IEC 61850-3 managed DIN-rail Ethernet switch, with 6 10/100BaseT(X) ports and 2 100BaseFX single-mode ports with SC connectors, 1 isolated power supply (48 VDC), -40 to 85°C operating temperature
PT-508-SS-SC-24 IEC 61850-3 managed DIN-rail Ethernet switch, with 6 10/100BaseT(X) ports and 2 100BaseFX single-mode ports with SC connectors, 1 isolated power supply (24 VDC), -40 to 85°C operating temperature
PT-508-SS-LC-HV IEC 61850-3 managed DIN-rail Ethernet switch, with 6 10/100BaseT(X) ports and 2 100BaseFX single-mode ports with LC connectors, 1 isolated power supply (88 to 300 VDC or 85 to 264 VAC), -40 to 85°C operating temperature
PT-508-SS-LC-48 IEC 61850-3 managed DIN-rail Ethernet switch, with 6 10/100BaseT(X) ports and 2 100BaseFX single-mode ports with LC connectors, 1 isolated power supply (48 VDC), -40 to 85°C operating temperature